Product Details & Technical Specifications
The Belimo R3020-4-S2 is an original Swiss-engineered HVAC component (Characterised control valve, 3-way, DN 20, Internal thread, Rp 3/4", PN 40, ps 1600 kPa, Kvs 4 m³/h, Fluid temperature -10...120°C [14...248°F]) in the Belimo Characterised Control Valves series, designed for commercial building automation, hydronic control, and air-handling systems.
Key Technical Highlights:
- Pattern: 3-way
- Kvs: 4 m³/h
- Fluid: Water, water with glycol up to max. 50% vol.
- Fluid temperature: -10...120°C [14...248°F]
- Fluid temperature note: At a fluid temperature of -10...2°C, a spindle heater or a valve neck extension is recommended., The allowed fluid temperature can be limited, depending on the type of actuator. Limitations can be found in the respective data sheets of the actuators.
Product Identification
- Brand: Belimo
- Part No. (SKU): R3020-4-S2
- Department: Valves and actuators
- Category: Characterised Control Valves
- Warranty: 5 Years Standard Manufacturer Warranty
Commercial & Logistics Details
- List Price (MSRP): €191.00 (EXW)
- Trade Price: €133.70
- Manufacturer HQ: Switzerland (CH)
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Pattern | 3-way |
| Kvs | 4 m³/h |
| Fluid | Water, water with glycol up to max. 50% vol. |
| Fluid temperature | -10...120°C [14...248°F] |
| Fluid temperature note | At a fluid temperature of -10...2°C, a spindle heater or a valve neck extension is recommended., The allowed fluid temperature can be limited, depending on the type of actuator. Limitations can be found in the respective data sheets of the actuators. |
| Differential pressure | ∆pmax 350 kPa |
| Close-off pressure | 1400 kPa |
| Differential pressure note | 200 kPa for low-noise operation |
| Flow characteristic {Tools} | A – AB: equal percentage; B – AB: linear |
| Leakage rate {Tools} | A – AB: air-bubble tight, leakage rate A; B – AB: Leakage class I, 1...2% of the Kvs value |
| Pipe connection | Internal thread |
Downloads & Technical Documentation
Belimo Official Portal ↗-
PDFDownload PDF ↗Technical data sheet – R3..xx-S..
-
PDFDownload PDF ↗Installation instructions – R2..-S.. / R3..-S..
-
PDFDownload PDF ↗EU Declaration of Conformity – R20.. / R30.. DN 15...32
-
PDFDownload PDF ↗Notes for project planning – 2-way / 3-way characterised control valves
-
PDFDownload PDF ↗Notes for project planning – General notes
-
PDFDownload PDF ↗Environmental Declaration – R3..
-
PDFDownload PDF ↗Application brochure – Air handling units
-
PDFDownload PDF ↗Application brochure – Heat Generation
-
PDFDownload PDF ↗Application information Cooling applications
-
PDFDownload PDF ↗Brochure - 8 reasons to use a characterised control valve
-
PDFDownload PDF ↗Brochure – Energy efficiency and comfort in buildings
-
PDFDownload PDF ↗Reference – CM Hasselt, Belgium
-
PDFDownload PDF ↗Reference – Emch+Berger ImmoConsult AG, Switzerland
-
PDFDownload PDF ↗Reference – Konvekta AG, Switzerland
-