Skip to product information
1 of 1

Siemens

Siemens DXR2.E09T-101A - Compact room automation station, BACnet/IP, 230 V, flat housing, 1 DI, 2 UI, 1 relay, 1 AO, 4 triac

Siemens DXR2.E09T-101A - Compact room automation station, BACnet/IP, 230 V, flat housing, 1 DI, 2 UI, 1 relay, 1 AO, 4 triac

Part No: DXR2.E09T-101A EAN: 7612914098634
Regular price €213,29
Sale price €213,29 Regular price €304,70
Ships in 3–5 business days
Quantity
Request a Quote
View full details

Product Details & Technical Specifications

The Siemens DXR2.E09T-101A is a compact, high-performance room automation station designed for demanding terminal control applications operating on 230 V AC line power. Featuring native BACnet/IP communication with an integrated dual-port Ethernet switch and KNX PL-Link expansion, the unit executes distributed HVAC control logic directly at the terminal level. Its optimized I/O footprint—including 4 triacs, 1 digital input, 2 universal inputs, 1 relay, and an analog output—enables precise thermal comfort and energy management in commercial spaces.

Recommended Applications:
  • Variable Air Volume (VAV) and Constant Air Volume (CAV) supply and exhaust air terminal regulation.
  • Two-pipe and four-pipe fan coil units (FCUs) with multi-stage electric heat or thermal control valves.
  • Integrated chilled ceiling and radiator heating systems paired with KNX PL-Link room sensor units.
Key Engineering Highlights:
  • High-Speed BACnet/IP Networking: Features an integrated 2-port Ethernet switch enabling cost-effective line topologies and ring redundancy without external network switches.
  • Direct 230 V AC Power Supply: Powered directly from 230 V AC mains (195.5...253 V), eliminating the requirement for external step-down control transformers inside ceiling plenums.
  • Targeted Terminal I/O Mix: Equipped with 4 silent AC 24 V triac outputs (0.15 A) for thermal actuators, a 250 V / 4 A relay for fan or auxiliary equipment control, and a DC 0...10 V analog output for modulating damper actuators.
  • KNX PL-Link & S-Mode Integration: Supplies onboard power and communication for direct connection to Siemens QMX series room operator units and peripheral KNX field sensors.

Compatibility & Installation: Housed in a compact IP20 flat enclosure (112 x 165 x 49 mm), the unit is engineered for direct damper shaft mounting, wall mounting, or installation inside ceiling voids and fan coil cabinets. It seamlessly integrates into Siemens Desigo CC and Desigo Control Point architectures, as well as third-party BACnet/IP building management systems.

Product Identification

  • Brand: Siemens
  • Product No. (ASN): DXR2.E09T-101A
  • Stock No. (SSN): S55376-C111
  • GTIN / EAN: 7612914098634
  • Warranty: 24 Months

Commercial & Logistics Details

  • List Price (MSRP): €304.70
  • Price: €213.29
  • Net Weight: 0.296 kg (296 g)
  • Country of Origin: Switzerland (CH)
  • Customs HS Code: 85371091
  • Minimum Order Qty (MOQ): 1 pc(s)
  • Sales Status: Saleable Product

Technical Specifications

Operating voltage AC 195.5...253 V, 230 V
Frequency 50/60 Hz
Power consumption 24 VA
Communication BACnet/IP , KNX PL-Link , KNX S-Mode
Universal inputs, number 2
Digital inputs, number 1
Analog outputs, number 1
Analog output, signal DC 0...10 V
Analog output, current 1 mA
Relay outputs, number 1
Relay output, switching voltage 250 V
Relay output, switching current 4 (3)A
Triac outputs, number 4
Triac output, switching voltage AC 24 V
Triac output, switching current 0.15 A
Mounting Inside rooms , Directly on the damper shaft , Front mounting
Degree of protection IP20
Dimensions (W x H x D) 112 x 165 x 49 mm

Downloads & Technical Documentation

Siemens HIT Official Portal ↗
  • PDF
    Datasheet: Compact room automation stations, BACnet/IP, AC 230 V, DXR2.E..
    View on Siemens HIT ↗
  • PDF
    Installation instruction: Desigo™ Room automation<BR/>Engineering, mounting and installation<BR/>PXC3.., DXR2.., DXR1..
    View on Siemens HIT ↗
  • DOC
    Application sheet: Fan coil unit with variable fan speed, heating and cooling coil (4 pipe) on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • DOC
    Application sheet: Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater, DXR2.E09T-101A
    View on Siemens HIT ↗
  • DOC
    Application sheet: Hot water radiator on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • DOC
    Application sheet: Chilled ceiling on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • DOC
    Application sheet: Chilled ceiling with hot water radiator on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • DOC
    Application sheet: Chilled/heated ceiling (2 pipe) with changeover on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • DOC
    Application sheet: Chilled ceiling with hot water radiator on triac output including lighting and blinds operation, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Fan coil unit with variable fan speed, heating and cooling coil (4 pipe) on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Hot water radiator on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Chilled ceiling on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Chilled ceiling with hot water radiator on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Chilled/heated ceiling (2 pipe) with changeover on triac output, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Chilled ceiling with hot water radiator on triac output including lighting and blinds operation, DXR2.E09T-101A
    View on Siemens HIT ↗
  • PDF
    Application sheet: Passive chilled beam (2 pipe) with hot water radiator on triac output
    View on Siemens HIT ↗
  • PDF
    Application sheet: Passive chilled/heating beam (2 pipe) with changeover on triac output
    View on Siemens HIT ↗
  • PDF
    Application sheet: Active chilled beam with variable fan, cooling coil and hot water radiator on triac output
    View on Siemens HIT ↗
  • PDF
    Declarations and Certificates: Information about BT eu.bac certificates
    View on Siemens HIT ↗
  • PDF
    Declaration of conformity: EU Declaration of Conformity DXR2 (230Vac)
    View on Siemens HIT ↗
  • PDF
    Declaration of conformity: RCM Supplier's Declaration DXR2
    View on Siemens HIT ↗
  • PDF
    Declaration of conformity: BACnet Certificate DXR2.Exx-x, DXR2.Mxx-x, DXR2.E17C, DXR2.E17CX
    View on Siemens HIT ↗
  • PDF
    Declaration of conformity: UK Declaration of Conformity DXR2xxx.xxx
    View on Siemens HIT ↗
  • PDF
    Environmental Documents: Compact room automation stations, DXR2.. 230V
    View on Siemens HIT ↗
  • PDF
    Environmental Documents: Siemens EcoTech Profile - DXR2 PXC3
    View on Siemens HIT ↗
  • PDF
    Environmental Documents: EPD Type II with LCA - Desigo - Building Automation - Automation stations PXC/DXR2, web interface PXG and edge devices CFG/CXG
    View on Siemens HIT ↗
  • PDF
    Environmental Documents: EPD Type III - Desigo- Building Automation - Automation stations PXC/DXR2, web interface PXG and edge devices CFG/CXG
    View on Siemens HIT ↗
  • EXTERNAL
    CAD and BIM product data (PartCommunity): European portfolio: click here for further information
    View on Siemens HIT ↗
  • EXTERNAL
    CAD and BIM product data (PartCommunity): Asia/Pacific portfolio: click here for further information
    View on Siemens HIT ↗
  • DOC
    Dimension Drawings: Desigo Room Room Automation Station DXR2 – 2D Graphics<BR/>Desigo Room Room Automation Station DXR2 – 3D Graphics
    View on Siemens HIT ↗
  • EXTERNAL
    Operating Instructions: ABT Site BOS
    View on Siemens HIT ↗
  • PDF
    Operating Instructions: Web Interface
    View on Siemens HIT ↗
  • PDF
    Assortment / System Descriptions: DXR2, DXR1 Desigo Room Automation Range Description
    View on Siemens HIT ↗