The Siemens DXR2.E17C-103A is a high-performance, BACnet/IP-enabled compact room automation station engineered for demanding room pressurization, fume hood control, and comprehensive HVAC terminal applications. Configured as a BTL-listed BACnet Advanced Application Controller (B-AAC), it executes deterministic control routines using dedicated SCOM high-resolution sensor communications and an integrated two-port Ethernet switch for resilient daisy-chain networking. Powered by 24 V AC, this station unifies fast-response airflow regulation with temperature, lighting, and shading management in critical environments.
- Laboratory fume hood face velocity management and dynamic exhaust airflow control
- Healthcare cleanroom and isolation ward differential pressure cascade control
- Critical life-science VAV terminal units requiring coordinated reheat and sash tracking
- High-Speed SCOM & Native BACnet/IP: Combines a dual-port Ethernet switch for seamless BACnet/IP daisy-chaining with dedicated SCOM interfaces for low-latency, high-precision differential pressure and airflow sensing.
- Versatile Mixed-Signal I/O: Delivers 4 universal inputs, 3 digital inputs, 4 analog outputs (0–10 V DC), and 4 triac outputs (24 V AC, 0.5 A) to simultaneously drive fast-acting dampers, reheat coils, and auxiliary equipment.
- KNX Field Bus Integration: Natively supports KNX PL-Link (with integrated bus power) and KNX S-Mode to directly connect smart room operator units, multisensors, and localized peripheral devices.
- B-AAC Certified Standard: Conforms to BTL BACnet Advanced Application Controller standards, ensuring high-fidelity interoperability with Siemens Desigo CC and third-party building automation systems.
Compatibility & Installation: Mounts on standard 35 mm DIN rails or flat surfaces within IP20-rated enclosures (180 x 105 x 60 mm). Interoperates seamlessly with Siemens KNX PL-Link room units, fast-acting 0–10 V damper actuators, and 24 V AC thermal or 3-point valve drives.
Product Identification
- Brand: Siemens
- Product No. (ASN): DXR2.E17C-103A
- Stock No. (SSN): S55376-C134
- GTIN / EAN: 7612914107107
- Warranty: 12 Months
Commercial & Logistics Details
- List Price (MSRP): €697.20
- Price: €488.04
- Net Weight: 0.364 kg (364 g)
- Country of Origin: Switzerland (CH)
- Customs HS Code: 85371091
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Operating voltage | AC 20.4...28.8 V, 24 V |
| Frequency | 50/60 Hz |
| Power consumption | 78 VA |
| Communication | BACnet/IP , KNX PL-Link , KNX S-Mode , SCOM |
| Universal inputs, number | 4 |
| Digital inputs, number | 3 |
| Analog outputs, number | 4 |
| Analog output, signal | DC 0...10 V |
| Analog output, current | 1 mA |
| Triac outputs, number | 4 |
| Triac output, switching voltage | 24 V |
| Triac output, switching current | 0.5 A |
| Mounting | Inside rooms , Front mounting |
| Degree of protection | IP20 |
| Dimensions (W x H x D) | 180 x 105 x 60 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Room Automation Station DXR2.E17C.. Technical Specification Sheet
-
PDFView on Siemens HIT ↗Installation instruction: Desigo™ Room automation<BR/>Engineering, mounting and installation<BR/>PXC3.., DXR2.., DXR1..
-
PDFView on Siemens HIT ↗Installation instruction: Room Automation Station DXR2.E17C.. Installation Instructions
-
PDFView on Siemens HIT ↗Application sheet: Fume hood with variable air volume flow control, vertical and horizontal sash and lighting
-
PDFView on Siemens HIT ↗Application sheet: Room pressurization with room air pressure sensor, air flow tracking and temperature control, heating and cooling coil or ceiling heating/chilled ceiling or radiator
-
PDFView on Siemens HIT ↗Application sheet: Room pressurization with room air pressure sensor, air volume flow tracking and temperature control, heating and cooling coil or ceiling heating/chilled ceiling or radiator with two room segments
-
PDFView on Siemens HIT ↗Application sheet: Fume hood with variable air volume flow control, stabilizing jet, vertical and horizontal sash with lighting
-
PDFView on Siemens HIT ↗Application sheet: Room pressurization through air flow tracking and temperature control, heating and cooling coil or ceiling heating/chilled ceiling or radiator
-
PDFView on Siemens HIT ↗Application sheet: Room pressurization with air volume flow tracking and temperature control, heating coil, cooling coil or ceiling heating/chilled ceiling or radiator with two room segments
-
PDFView on Siemens HIT ↗Declarations and Certificates: VAV system CET solution for laboratories and cleanroom
-
PDFView on Siemens HIT ↗Declarations and Certificates: EN14175-6 Certificate HLBHA00200-Damper
-
PDFView on Siemens HIT ↗Declarations and Certificates: EN14175-6 Certificate HLBHA00250-Damper
-
PDFView on Siemens HIT ↗Declaration of conformity: DXR Lab IP Controller Declaration of Conformity
-
PDFView on Siemens HIT ↗Declaration of conformity: BACnet Certificate DXR2.Exx-x, DXR2.Mxx-x, DXR2.E17C, DXR2.E17CX
-
PDFView on Siemens HIT ↗Declaration of conformity: 8265 DXR Lab Controller ACMA N474
-
PDFView on Siemens HIT ↗Declaration of conformity: OAVS AMCA Declaration of Conformity
-
PDFView on Siemens HIT ↗Declaration of conformity: UK Declaration of Conformity DXR2xxx.xxx DXP2xxx.xxx
-
PDFView on Siemens HIT ↗Environmental Documents: Compact room automation stations, DXR2.. 24V
-
PDFView on Siemens HIT ↗Environmental Documents: Siemens EcoTech Profile - DXR2 PXC3
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type II with LCA - Desigo - Building Automation - Automation stations PXC/DXR2, web interface PXG and edge devices CFG/CXG
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type III - Desigo- Building Automation - Automation stations PXC/DXR2, web interface PXG and edge devices CFG/CXG
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): Asia/Pacific portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗Operating Instructions: ABT Site BOS
-
PDFView on Siemens HIT ↗Operating Instructions: Web Interface
-
PDFView on Siemens HIT ↗Assortment / System Descriptions: DXR2, DXR1 Desigo Room Automation Range Description