Product Details & Technical Specifications
The Siemens QAM2171.040 is an active duct temperature sensor engineered to acquire precise airflow temperatures across a span of -50 to +50 °C in commercial HVAC systems. Utilizing an internal Pt1000 sensing element coupled with an integrated transmitter, the unit converts thermal measurements into an interference-resistant DC 4...20 mA current output across a rigid 400 mm probe. It delivers stable process feedback for supply, return, or mixed air streams under challenging air velocity conditions.
Recommended Applications:
- Supply and extract air temperature monitoring in central air handling units (AHUs).
- Mixed air and economizer damper modulation for precise outdoor air enthalpy control.
- Frost monitoring and low-temperature limit detection in intake air ducts.
Key Engineering Highlights:
- Noise-Immune Signal: Transmits an active DC 4...20 mA signal over long wiring distances without voltage drop or signal degradation, simplifying PLC/DDC integration.
- Wide Measurement Range: Calibrated for -50 to 50 °C with high factory accuracy (±0.9 K) and a rapid 30-second thermal response time at 2 m/s airflow.
- Flexible Power Compatibility: Operates across a wide DC 13.5…35 V supply range with low nominal power consumption of 1 VA.
- Rugged Field Construction: Features an IP54-rated housing with standard screw terminals and a 303…363 mm adjustable immersion depth.
Compatibility & Installation: Mounts directly to duct walls via an adjustable mounting flange and connects to any third-party or Siemens Desigo DDC controller accepting 2-wire DC 4...20 mA analog inputs.
Product Identification
- Brand: Siemens
- Product No. (ASN): QAM2171.040
- Stock No. (SSN): BPZ:QAM2171.040
- GTIN / EAN: 4047625019891
- Warranty: 60 Months
Commercial & Logistics Details
- List Price (MSRP): €163.80
- Price: €101,56
- Net Weight: 0.175 kg (175 g)
- Country of Origin: China (CN)
- Customs HS Code: 85332100
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Signal output temperature | DC 4...20 mA |
| Operating voltage | DC 13.5…35 V |
| Power consumption | 1 VA |
| Sensing element, temperature | Pt1000 |
| Measuring range, temperature | -50…50 °C |
| Measurement accuracy | At -50…50 °C: ±0.9 K |
| Time constant | Air v=2 m/s: 30 s |
| Immersion length | 303…363 mm |
| Probe length | 400 mm |
| Connection, electrical | Screw terminals |
| Type of fixing | Flange |
| Degree of protection | IP54 |
| Dimensions (W x H x D) | 80 x 88 x 39 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Duct temperature sensors QAM2161.040, QAM2171.040, QAM3163.040, QAM3173.040, with 0…5 V output
-
PDFView on Siemens HIT ↗Other datasheet: Duct temperature sensors QAM2161.040, QAM2171.040, w/o 0…5 V output
-
PDFView on Siemens HIT ↗Declarations and Certificates: Testreport/ Werkszeugnis (T + RF Sensors)
-
PDFView on Siemens HIT ↗Declaration of conformity: EU Declaration of Conformity QAM21xx.40, QAM31xx.40
-
PDFView on Siemens HIT ↗Declaration of conformity: RCM Supplier's declaration QAMx1... / QFM...
-
PDFView on Siemens HIT ↗Declaration of conformity: KC Certificate QAM2171.040
-
PDFView on Siemens HIT ↗Declaration of conformity: UK Declaration of conformity for QAM2161.040, QAM2171.040, QAM3163.040, QAM3173.040
-
PDFView on Siemens HIT ↗Declaration of conformity: Test report MTBF for QA..
-
PDFView on Siemens HIT ↗Environmental Documents: Duct Temperature Sensors, Immersion Temp.Sensors, Outside Temp.Sensors
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type III - Wired Sensors - Duct and Immersion Sensors QAC…, QAE…, QAM…,QBM…,QFM…
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type II with LCA - Wired Sensors - Duct and Immersion Sensors QAC…, QAE…, QAM…, QBM…, QFM…
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): Asia/Pacific portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): Americas portfolio: click here for further information
-
PDFView on Siemens HIT ↗Mounting instruction: Immersion and Duct temperature sensor QAE.., QAM.., with 0…5 V output
-
PDFView on Siemens HIT ↗Mounting instruction: Immersion and Duct temperature sensor QAE.., QAM.., w/o 0…5 V output