Product Details & Technical Specifications
The Siemens QFM1660 is an active duct-mounted sensor engineered for continuous, simultaneous measurement of relative humidity and temperature in air handling and ventilation ductwork. Utilizing high-stability sensing elements across an immersion depth of 186 mm, the device converts measured values into dual, linear DC 0...10 V analog output signals for direct interface with central building automation and DDC control systems.
Recommended Applications:
- Commercial air handling units (AHUs) managing supply, extract, or return air conditions
- Economizer control loops and demand-controlled ventilation (DCV) requiring precise psychrometric monitoring
- Humidity-critical building zones such as cleanrooms, data centers, and healthcare facilities operating within 10...90 % r.h.
Key Engineering Highlights:
- Dual DC 0...10 V Outputs: Provides individual, calibrated analog signals for both relative humidity (10...90 % r.h.) and temperature measurement.
- Low-Power SELV Operation: Functions efficiently on AC 24 V or DC 19...30 V with an energy-conscious 1 VA power consumption profile.
- Optimized Duct Immersion: Features a 186 mm probe design to ensure accurate mid-duct core airflow sampling with a temperature accuracy of ±0.8 K at 25 °C and ±5 % r.h. for humidity.
Compatibility & Installation: Mounts directly through circular or rectangular sheet metal ductwork via an adjustable mounting flange and connects natively to any DDC controller or BMS supporting standard DC 0...10 V sensor inputs, including Siemens Desigo.
Product Identification
- Brand: Siemens
- Product No. (ASN): QFM1660
- Stock No. (SSN): S55720-S198
- GTIN / EAN: 7612914086211
- Warranty: 60 Months
Commercial & Logistics Details
- List Price (MSRP): €147.40
- Price: €91,39
- Net Weight: 0.086 kg (86 g)
- Country of Origin: China (CN)
- Customs HS Code: 90258040
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Operating voltage | AC 19.2...28.8 V, 24 V, 19...30 V |
| Voltage supply | External SELV power supply AC/DC 24 V nominal |
| Power consumption | 1 VA |
| Measurement range humidity | 10...90 % r.h. |
| Measurement accuracy | 25 °C: ±0.8 K, At 20...25 % r.h., 10...90 % r.h.: ±5 % r.h.±5 % r.h. |
| Immersion length | 186 mm |
| Analog output, signal | DC 0...10 V |
| Signal output temperature | DC 0...10 V |
| Signal output humidity | DC 0...10 V |
| Display | No display |
| Dimensions (W x H x D) | 72 x 56 x 222 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Duct Humidity and Temperature Sensor QFM1660, QFM1661
-
PDFView on Siemens HIT ↗Declaration of conformity: EU Declaration of conformity QFM16xx
-
PDFView on Siemens HIT ↗Declaration of conformity: UK Declaration of conformity for QFM16xx
-
PDFView on Siemens HIT ↗Declaration of conformity: Test report MTBF for QFM.., QFA..
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type III - Wired Sensors - Duct and Immersion Sensors QAC..., QAE..., QAM...,QBM...,QFM...
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type II with LCA - Wired Sensors - Duct and Immersion Sensors QAC..., QAE..., QAM..., QBM..., QFM...
-
PDFView on Siemens HIT ↗Environmental Documents: Environmental Product Declaration QFM1660, QFM1661
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): Asia/Pacific portfolio: click here for further information