Product Details & Technical Specifications
The Siemens QPM1100 is a duct-mounted air quality sensor engineered to measure volatile organic compounds (VOC) and mixed gases across a 0 to 100% relative scale. Operating on a solid-state sensing element, it reliably quantifies indoor air contamination such as body odors, tobacco smoke, and outgassing from materials to modulate outdoor air intake. Built for continuous operation in demand-controlled ventilation (DCV) loops, this unit provides precise environmental tracking for comfort applications.
- Demand-controlled ventilation (DCV) in air handling units (AHUs) serving offices, schools, and commercial facilities
- Extract and return air duct monitoring in conference spaces, gymnasiums, and hospitality venues subject to variable occupancy
- Economizer and dynamic fresh air intake optimization in commercial VAV central ventilation systems
- Multi-Signal Analog Output: Provides selectable DC 0...10 V, DC 0...5 V, or DC 4...20 mA outputs for direct compatibility with industry-standard DDC controllers.
- Versatile Power Supply: Accepts AC 24 V or DC 15...35 V with a nominal power consumption of only 2 VA, simplifying field power distribution.
- High Airflow Tolerance: Robust probe architecture operates accurately at duct velocities up to 10 m/s across an ambient span of -5 °C to 45 °C.
- Adjustable Immersion Depth: Integrated immersion tube allows quick adjustment between 70 mm and 135 mm to achieve optimal center-stream duct positioning.
Compatibility & Installation: Mounts directly to sheet metal ductwork using the included adjustable immersion flange (70...135 mm insertion depth) and wires via screw terminals to any Siemens Desigo, Synco, or third-party BMS controller.
Product Identification
- Brand: Siemens
- Product No. (ASN): QPM1100
- Stock No. (SSN): S55720-S123
- GTIN / EAN: 7612914075956
- Warranty: 60 Months
Commercial & Logistics Details
- List Price (MSRP): €261.60
- Price: €183.12
- Net Weight: 0.18 kg (180 g)
- Country of Origin: China (CN)
- Customs HS Code: 90262080
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Operating voltage | AC 24 V, DC 15...35 V |
| Power consumption | 2 VA |
| Immersion length | 70...135 mm |
| Analog output, signal | DC 0...10 V, DC 0...5 V, DC 4...20 mA |
| Measuring range | 0...100 % VOC |
| Permissible air velocity | 10 m/s |
| Ambient temperature, operation | -5...45 °C |
| Connection, electrical | Screw terminals |
| Dimensions (W x H x D) | 80 x 88 x 243 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Duct Air Quality Sensors QPM21..
-
PDFView on Siemens HIT ↗Declarations and Certificates: Testreport/ Werkszeugnis (T + RF Sensors)
-
PDFView on Siemens HIT ↗Declaration of conformity: EU Declaration of Conformity QPMxxxx
-
PDFView on Siemens HIT ↗Declaration of conformity: RCM Supplier's Declaration QPA../QPM../QFA..
-
PDFView on Siemens HIT ↗Declaration of conformity: UK Declaration of conformity for QPMxxxx
-
PDFView on Siemens HIT ↗Declaration of conformity: Test report MTBF for QP..
-
PDFView on Siemens HIT ↗Environmental Documents: Duct Air Quality Sensor
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type III - Wired Sensors - Duct and Immersion Sensors QAC..., QAE..., QAM...,QBM...,QFM...
-
PDFView on Siemens HIT ↗Environmental Documents: EPD Type II with LCA - Wired Sensors - Duct and Immersion Sensors QAC..., QAE..., QAM..., QBM..., QFM...
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): Asia/Pacific portfolio: click here for further information
-
PDFView on Siemens HIT ↗Mounting instruction: Sensor mounting for QPA.., QPM..
-
PDFView on Siemens HIT ↗Mounting instruction: Duct air quality sensor CO2/ temperature / rel. Humidity / VOC QPM11..., QPM21...