Product Details & Technical Specifications
The Siemens QPM2180 is a duct-mounted air quality sensor engineered to measure carbon dioxide (CO₂) concentration and passive temperature within commercial ventilation systems. Utilizing optical infrared absorption (NDIR) technology, it accurately evaluates CO₂ levels across a 0 to 2000 ppm range to optimize demand-controlled ventilation (DCV). Designed for extract and supply air ducts, the unit operates reliably in air velocities up to 10 m/s to ensure energy-efficient building air exchange.
- Demand-controlled ventilation (DCV) loops in central air handling units (AHUs) serving schools, conference rooms, and commercial offices.
- Return and extract air monitoring for commercial building automation systems (BAS) to regulate outdoor air dampers.
- Combined IAQ and thermal monitoring in variable air volume (VAV) supply air streams to meet ASHRAE 62.1 fresh air standards.
- Multi-Signal Output Flexibility: Delivers field-selectable analog outputs of DC 0...10 V, DC 0...5 V, or DC 4...20 mA for CO₂, alongside an integrated passive temperature element.
- Adjustable Immersion Depth: Features a versatile 100 to 165 mm probe immersion length for precise centerline positioning within diverse duct dimensions.
- Wide Aerodynamic Range: Engineered to withstand and measure accurately within duct air velocities reaching up to 10 m/s without signal degradation.
- Broad Power Supply Tolerance: Operates efficiently on AC 24 V or DC 15...35 V power supplies with a low nominal power consumption of 2 VA.
Compatibility & Installation: Mounts directly to sheet metal ductwork via an adjustable immersion mounting flange, connecting to standard DDC inputs and building automation systems via robust screw terminals.
Product Identification
- Brand: Siemens
- Product No. (ASN): QPM2180
- Stock No. (SSN): S55720-S124
- GTIN / EAN: 7612914075963
- Warranty: 60 Months
Commercial & Logistics Details
- List Price (MSRP): €580.80
- Price: €406.56
- Net Weight: 0.198 kg (198 g)
- Country of Origin: China (CN)
- Customs HS Code: 90271010
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Operating voltage | AC 24 V, DC 15...35 V |
| Power consumption | 2 VA |
| Immersion length | 100...165 mm |
| Analog output, signal | DC 0...10 V, DC 0...5 V, DC 4...20 mA |
| Measuring range | 0...2000 ppm CO₂ |
| Permissible air velocity | 10 m/s |
| Ambient temperature, operation | -5...45 °C |
| Connection, electrical | Screw terminals |
| Dimensions (W x H x D) | 80 x 88 x 278 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Duct Air Quality Sensors QPM21..
-
PDFView on Siemens HIT ↗Declarations and Certificates: Testreport/ Werkszeugnis (T + RF Sensors)
-
PDFView on Siemens HIT ↗Declaration of conformity: EU Declaration of Conformity QPMxxxx
-
PDFView on Siemens HIT ↗Declaration of conformity: RCM Supplier's Declaration QPA../QPM../QFA..
-
PDFView on Siemens HIT ↗Declaration of conformity: UK Declaration of conformity for QPMxxxx
-
PDFView on Siemens HIT ↗Declaration of conformity: Test report MTBF for QP..
-
PDFView on Siemens HIT ↗Environmental Documents: Duct Air Quality Sensor
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): Asia/Pacific portfolio: click here for further information
-
PDFView on Siemens HIT ↗Mounting instruction: Sensor mounting for QPA.., QPM..
-
PDFView on Siemens HIT ↗Mounting instruction: Duct air quality sensor CO2/ temperature / rel. Humidity / VOC QPM11..., QPM21...