Product Details & Technical Specifications
The Siemens QSA2700 is an optical room sensor engineered to measure indoor particulate matter concentrations, providing real-time detection of both PM2.5 and PM10 fractions for demand-controlled ventilation (DCV). Utilizing precision laser scattering principles, the device delivers accurate particle detection across indoor spaces to safeguard occupant health and optimize air filtration efficiency. It integrates seamlessly into modern building management systems through both analog DC 0...10 V signals and digital Modbus RTU communication.
- Demand-controlled ventilation (DCV) loops in commercial offices, educational facilities, and healthcare spaces modulating AHU outdoor air and recirculation dampers.
- Air handling unit (AHU) and dedicated outdoor air system (DOAS) zones requiring active indoor air quality tracking and multi-stage filter performance monitoring.
- Green building compliance monitoring in facilities engineered to meet LEED, WELL Building Standard, or RESET indoor particulate air quality thresholds.
- Dual Output Architecture: Features both a DC 0...10 V analog output for direct DDC loop control and a Modbus RTU (RS-485) network interface for comprehensive BMS monitoring.
- Simultaneous PM2.5 & PM10 Detection: Provides high-precision optical measurement of fine combustion particulates and respirable coarse dust fractions.
- Visual Service Indication: Equipped with a 3-color front-panel LED for instantaneous room-level IAQ classification and sensor maintenance alerts.
- Standard Low-Voltage Supply: Operates on standard AC/DC 24 V line power and includes a Micro-USB service port for streamlined field configuration and diagnostics.
Compatibility & Installation: Engineered with a compact 86 x 86 mm architectural footprint for flush mounting on standard recessed electrical back-boxes or direct surface installation, with native communication compatibility for Siemens Desigo and third-party Modbus RTU networks.
Product Identification
- Brand: Siemens
- Product No. (ASN): QSA2700
- Stock No. (SSN): S55720-S457
- GTIN / EAN: 4047625003081
- Warranty: 60 Months
Commercial & Logistics Details
- List Price (MSRP): €410.80
- Price: €287.56
- Net Weight: 0.134 kg (134 g)
- Country of Origin: China (CN)
- Customs HS Code: 90271010
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Operating voltage | AC/DC 24 V, DC 24 V |
| Connection cable | Micro USB |
| Analog outputs | DC 0...10 V |
| Display | 3-color LED service indication |
| Communication | Modbus RTU (RS-485) |
| Dimensions (W x H x D) | 86 x 86 x 30 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Fine Dust Room Sensors QSA2700D/QSA2700
-
PDFView on Siemens HIT ↗Declarations and Certificates: Fine Dust Room Sensors QSA2700D/QSA2700 EPD
-
PDFView on Siemens HIT ↗Declaration of conformity: EU DoC for PM2.5 Fine Dust Sensor
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): Americas portfolio: click here for further information
-
PDFView on Siemens HIT ↗Basic documentation: Fine Dust Room Sensors QSA2700D/QSA2700
-
PDFView on Siemens HIT ↗Mounting instruction: Fine Dust Room Sensors QSA2700D/QSA2700