Product Details & Technical Specifications
The Siemens WSN525-FE is a high-precision, wall-mountable ultrasonic energy meter engineered for autonomous thermal measurement in combined heating and cooling hydronic circuits. Operating on transit-time acoustic measurement paired with Pt500 platinum resistance sensors, it provides non-intrusive, static volumetric flow calculation immune to mechanical wear and particulate clogging. Designed for return-pipe integration, the unit features an internal 3.6 V lithium battery and Wireless M-Bus RF communication for seamless submetering and automated energy telemetry.
- Commercial tenant submetering and utility allocation in 2-pipe changeover heating and cooling distribution systems.
- Decentralized district heating and chilled water building substations requiring MID Class 2 fiscal billing accuracy.
- Hydronic heat pump networks, air handling unit (AHU) coils, and fan coil systems requiring accurate thermal load verification.
- Static Ultrasonic Flow Measurement: Features a high-tech composite flow sensor with no moving parts, delivering MID Class 2 compliance (EN 1434) at a nominal flow rate of Qp 2.5 m³/h with minimal hydraulic head loss.
- Integrated Wireless M-Bus RF: Equipped with open-standard M-Bus radio telemetry for automated meter reading (AMR), facilitating drive-by or stationary wireless data harvesting without secondary signal wiring.
- Long-Life Autonomous Power: Powered by an internal 3.6 V DC lithium cell offering an 11-year operational life, eliminating field maintenance and continuous external control voltage dependencies.
- High-Precision Pt500 Sensing: Ships with paired Ø 5.2 x 45 mm Pt500 immersion sensors (1.5 m cable) for accurate differential temperature calculation across fluid ranges from 5 °C to 90 °C.
Compatibility & Installation: Engineered for PN 16 return-line pipe mounting with standard G 1" threaded connections and a 130 mm overall installation length. Wirelessly interoperates with any OMS-compliant wireless M-Bus receiver or central energy management gateway operating under EN 13757-4.
Product Identification
- Brand: Siemens
- Product No. (ASN): WSN525-FE
- Stock No. (SSN): S55561-F283
- GTIN / EAN: 4047625012793
- Warranty: 24 Months
Commercial & Logistics Details
- List Price (MSRP): €363.00
- Price: €254.10
- Net Weight: 0.494 kg (494 g)
- Country of Origin: Germany (DE)
- Customs HS Code: 90268020
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Measurement accuracy | MID class 2 |
| Standard | EN 1434 |
| Voltage supply | Lithium battery |
| Operating life of battery | 11 years |
| Operating voltage | DC 3.6 V |
| PN class | PN 16 |
| Nominal flow rate | 2.5 m³/h |
| Mounting length | 130 mm |
| Measuring range, temperature | Processor unit: 0...180 °C, Flow measuring section: 5...90 °C |
| Sensing element, temperature | Pt500 |
| Sensor | Pocket long 5.2 x 45 mm |
| Connecting thread | G 1" |
| Cable length, sensor | 1.5 m |
| Due Date | 01.01 |
| Communication | M-bus RF |
| Display | kWh |
| Temperature range electronic unit | 0...180 °C |
| Temperature range volume measuring section | 5...90 °C |
| Mounting location | Meter: return , Sensor in the flow: selectable, directly/indirectly immersed , Sensor in the return: integrated in the return, directly immersed |
| Dimensions (W x H x D) | 130 x 77 x 116 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Ultrasonic compact heat and heat/cooling energy meters WS.5.., WS.6..
-
PDFView on Siemens HIT ↗Installation instruction: Battery exchange instructions WS.5, WS.6
-
PDFView on Siemens HIT ↗Declarations and Certificates: Safety Data Sheet WSM506-BE
-
PDFView on Siemens HIT ↗Declaration of conformity: EU Declaration of Conformity WSM5xx
-
PDFView on Siemens HIT ↗Environmental Documents: WSM5..-FE, WSN5..-FE
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
PDFView on Siemens HIT ↗Basic documentation: Key Handling Portal Web: User Guide
-
PDFView on Siemens HIT ↗Basic documentation: Key Management Assistl App: User Guide
-
PDFView on Siemens HIT ↗Operating Instructions: Ultrasonic heat and cold meter WS.5..