Product Details & Technical Specifications
The Siemens WSN606-BE is a static ultrasonic heat and cooling energy meter engineered for high-precision thermal consumption acquisition in commercial and residential hydronic circuits. Operating on the ultrasonic transit-time principle with paired Pt500 temperature sensors, it continuously measures fluid velocity and differential temperature without mechanical wear or system head loss. MID Class 2 approved and factory-configured for return-line installation, the unit features an integrated M-bus communication module and an onboard lithium battery providing up to 11 years of continuous operation.
- Tenant submetering and utility allocation in commercial office spaces and multi-dwelling residential buildings.
- Decentralized fan coil units (FCU) and chilled water/heating water terminal equipment monitoring.
- District heating and cooling substations requiring accurate low-flow metering down to nominal flow rate Qp 0.6 m³/h.
- Wear-Free Static Measurement: Solid-state ultrasonic flow measurement eliminates moving parts, drastically reducing vulnerability to particulate debris and sustaining calibration integrity to MID Class 2 / EN 1434 standards.
- Integrated Automated Meter Reading (AMR): Native wired M-bus interface enables direct transmission of thermal consumption (kWh), volumetric flow, temperatures, and diagnostic alarms to building automation systems.
- Autonomous 11-Year Power Supply: Powered by an internal 3.6 V DC lithium battery, cutting installation labor by eliminating external field power supplies and line-voltage wiring.
- High-Pressure Hydronic Build: Rugged brass flow section rated for PN 16 system pressures, accommodating fluid temperatures from -5 °C to 50 °C in cooling/heating loops with minimal pressure drop.
Compatibility & Installation: Engineered with a compact 110 mm overall length and standard G ¾" male thread connections for seamless in-line return pipe mounting. Paired Pt500 sensors (Ø 5.2 x 45 mm, 1.5 m leads) install via direct immersion or compatible M10 / standard EN 1434 immersion pockets.
Product Identification
- Brand: Siemens
- Product No. (ASN): WSN606-BE
- Stock No. (SSN): S55561-F266
- GTIN / EAN: 4047625006655
- Warranty: 24 Months
Commercial & Logistics Details
- List Price (MSRP): €412.00
- Price: €288.40
- Net Weight: 0.829 kg (829 g)
- Country of Origin: Germany (DE)
- Customs HS Code: 90268020
- Minimum Order Qty (MOQ): 1 pc(s)
- Sales Status: Saleable Product
Technical Specifications
| Type of Meter | Heat , Cooling |
| Measurement accuracy | MID class 2 , EN 1434 |
| Standard | EN 1434 |
| Voltage supply | Lithium battery |
| Operating life of battery | 11 years |
| Operating voltage | DC 3.6 V |
| PN class | PN 16 |
| Nominal flow rate | 0.6 m³/h |
| Mounting length | 110 mm |
| Measuring range, temperature | Processor unit: 0...180 °C, Flow measuring section: -5...50 °C |
| Sensing element, temperature | Pt500 |
| Sensor | 5.2 x 45 mm |
| Connecting thread | G ¾" |
| Cable length, sensor | 1.5 m |
| Due Date | 01.01 |
| Communication | M-bus |
| Display | kWh |
| Mounting location | Meter: return , Sensor in the flow: selectable, directly/indirectly immersed , Sensor in the return: integrated in the return, directly immersed |
| Dimensions (W x H x D) | 116 x 71 x 32 mm |
Downloads & Technical Documentation
Siemens HIT Official Portal ↗-
PDFView on Siemens HIT ↗Datasheet: Ultrasonic compact heat and heat/cooling energy meters WS.5.., WS.6..
-
PDFView on Siemens HIT ↗Installation instruction: Protection against transients
-
PDFView on Siemens HIT ↗Installation instruction: Battery exchange instructions WS.5, WS.6
-
PDFView on Siemens HIT ↗Declarations and Certificates: Safety Data Sheet WSM506-BE
-
PDFView on Siemens HIT ↗Declaration of conformity: EU Declaration of Conformity WSM6xx
-
PDFView on Siemens HIT ↗Environmental Documents: WSM6..
-
EXTERNALView on Siemens HIT ↗CAD and BIM product data (PartCommunity): European portfolio: click here for further information
-
PDFView on Siemens HIT ↗Basic documentation: Key Handling Portal Web: User Guide
-
PDFView on Siemens HIT ↗Basic documentation: Key Management Assistl App: User Guide
-
PDFView on Siemens HIT ↗Operating Instructions: Ultrasonic heat and heat / cooling meter WSx6..