Skip to product information
1 of 1

Siemens

Siemens WSN853-FDBBF3A - Ultrasonic heat/cooling energy meter, Qp = 6 m3/h, wall-mounted, mounting length 260 mm, connection thread G 1 ¼ ", sensor M10x1 mm x 38 mm, M-bus communication, 2 pulse inputs, battery life 11 years

Siemens WSN853-FDBBF3A - Ultrasonic heat/cooling energy meter, Qp = 6 m3/h, wall-mounted, mounting length 260 mm, connection thread G 1 ¼ ", sensor M10x1 mm x 38 mm, M-bus communication, 2 pulse inputs, battery life 11 years

Part No: WSN853-FDBBF3A EAN: 4047625018627
Regular price €640,50
Sale price €640,50 Regular price €915,00
Ships in 3–5 business days
Quantity
Request a Quote
View full details

Product Details & Technical Specifications

The Siemens WSN853-FDBBF3A is an ultrasonic thermal energy meter engineered for static, high-accuracy metering in combined hydronic heating and chilled water loops. Operating on transit-time acoustic measurement paired with matched Pt500 sensors, the device provides continuous, wear-free consumption logging compliant with MID Class 2 and EN 1434 standards. It is configured for return-pipe installation with a nominal flow rate of 6 m³/h, delivering reliable revenue-grade data without moving mechanical components.

Recommended Applications:
  • District heating and cooling substations requiring MID Class 2 fiscal billing accuracy
  • Commercial hydronic secondary loops serving air handling units (AHUs) and large central fan coil networks
  • Tenant submetering and multi-zone thermal energy monitoring in commercial office towers and logistics centers
Key Engineering Highlights:
  • Wear-Free Ultrasonic Flow Measurement: Solid-state acoustic transit-time technology prevents mechanical degradation, head loss, and fouling from particulates in PN16 systems.
  • Integrated M-Bus & Auxiliary Pulse Inputs: Native M-Bus interface supports automated meter reading (AMR), complemented by two pulse inputs to aggregate secondary utility meters into one bus drop.
  • Extended 11-Year Battery Autonomous Operation: Internal 3.6 V DC lithium cell eliminates the need for external control wiring, ensuring uncompromised logging across multi-year audit cycles.
  • Streamlined Return-Pipe Assembly: Features a 260 mm body with G 1¼" threading and an integrated flow-section Pt500 pocket, cutting down piping labor and extra tap points.

Compatibility & Installation: Designed for standard inline return-pipe mounting via G 1¼" union fittings with a 260 mm face-to-face dimension, interfacing seamlessly with EN 13757 M-Bus networks and supervisory BMS platforms.

Product Identification

  • Brand: Siemens
  • Product No. (ASN): WSN853-FDBBF3A
  • Stock No. (SSN): S55561-F287
  • GTIN / EAN: 4047625018627
  • Warranty: 24 Months

Commercial & Logistics Details

  • List Price (MSRP): €915.00
  • Price: €640.50
  • Net Weight: 1.792 kg (1792 g)
  • Country of Origin: Germany (DE)
  • Customs HS Code: 90268020
  • Minimum Order Qty (MOQ): 1 pc(s)
  • Sales Status: Saleable Product

Technical Specifications

Type of Meter Cooling , Heat
Measurement accuracy MID class 2
Standard EN 1434
Voltage supply Lithium battery
Operating life of battery 11 years
Operating voltage DC 3.6 V
PN class PN 16
Nominal flow rate 6 m³/h
Mounting length 260 mm
Measuring range, temperature Processor unit: 0...180 °C, 130 °C
Sensing element, temperature Pt500
Sensor M10; 1 x 38 mm
Connecting thread G 1¼"
Cable length, sensor 1.5 m
Due Date 01.01
Communication M-bus
Display kWh
Mounting location Meter mounting: In return , Sensor mounting: Return sensor, integrated in the flow measuring section
Dimensions (W x H x D) 44 x 138 x 105 mm

Downloads & Technical Documentation

Siemens HIT Official Portal ↗